C-BT Enclosure for Installation on Pole-Mounted Transformer Station (P.T.P.)

The C-BT enclosure – N0ST0131 series is designed for pole-mounted installation in transformer stations, ensuring protection, ventilation, and full compatibility with the ENEL B-CBT base for C-BT concentrators.
Manufactured in SMC fiberglass and compliant with ENEL technical specifications, it guarantees maximum reliability for LV distribution networks.

C-BT Enclosure for Installation on Pole-Mounted Transformer Station (P.T.P.)

Available Variants

ENEL version with SC/T lock

Parameter Value Unit
Material SMC (fiberglass), grey RAL 7001
Reference standards CEI EN 61439-5 (/A1), DS4931 Enel
Flame resistance > 80 punti (Enel DS 4974)
Surface tracking resistance PTI 500 (IEC 60112)
Impact resistance 20 J (CEI EN 61439-5)
Degree of protection P 34D
ENEL specifications DH 2480 – Registration No. 288041

Technical Specifications – C-BT Enclosure for Pole-Mounted Transformer Station (P.T.P.)

Structure and Materials

The enclosure is manufactured in SMC (Sheet Moulding Compound) fiberglass, grey RAL 7001, ensuring high mechanical strength, resistance to weathering, and excellent dielectric insulation. The structure is designed for wall or pole mounting and for housing the ENEL B-CBT base intended for the C-BT concentrator.

Functionality

The enclosure features a ribbed door with 120° opening and full removability, allowing easy internal access. Passive ventilation is provided through side louvers with insect mesh, also suitable for installing an optional fan. The lower section includes two pre-drilled cable entry holes for power supply and wiring, compatible with PG36 and PG21 glands. The enclosure is equipped with an ENEL lock system acting on three locking points.

Compliance

The enclosure complies with CEI EN 61439-5 (/A1) and ENEL prescriptions DS4931, DH2480, and DS4974, covering flame resistance, impact resistance, and degree of protection. The degree of protection is IP34D according to CEI EN 60529, with surface tracking resistance PTI 500 in accordance with IEC 60112.

ENEL references

DS 4931, DS 4974.

Versatile Applications

  • Installation of C-BT concentrators in pole-mounted transformer stations (PTP)

  • Housing of the ENEL B-CBT base

  • Measurement and remote control infrastructures on LV networks

  • Outdoor installations requiring ventilation and IP34D protection

CONTACT US