Current Transformer Assemblies and Cable Guides for LV Semi-Indirect Supplies

NTET current transformer (CT) assemblies and cable guides for low-voltage semi-indirect supplies ensure safe integration and full compliance with Enel standards for GET4S, GISS and GME/BS metering systems.
Robust fiberglass solutions, suitable for wall mounting or installation inside dedicated enclosures.

Current Transformer Assemblies and Cable Guides for LV Semi-Indirect Supplies
Current Transformer Assemblies and Cable Guides for LV Semi-Indirect Supplies
Current Transformer Assemblies and Cable Guides for LV Semi-Indirect Supplies

Available Variants

Unit for semi-indirect supplies up to 200 kW with CT ratio 125/5 A/A. Complete structure with fiberglass base and cover, integrated CT block and input/output terminals. Suitable for wall installation or inside DS4558 / C4M / C3M enclosures.

Parameter Value Unit
Base dimensions 464 mm
Height 501 mm
Depth 183 mm
Material Reinforced polyester fiberglass resin, RAL 7040
Fire reaction class Class 1 UNI 8457
Smoke opacity ≤ 1,5 CEI 20-37 / CEI 20-38/1
Toxic / corrosive gases ≤ 2 CEI 20-37 / CEI 20-38/1
PTI ≥ 500
CT block material PA66 G25 V0 halogen-free CTI 600V
Rated voltage 400 V
Rated frequency 50 Hz
CT ratio 125/5 A
Assembly rated current 500 A
Technical standard Enel DMI031006

Technical Specifications – CT Assembly 200 kW

Structure and materials

  • Reinforced polyester fiberglass resin enclosure, RAL 7040
  • Internal components made of self-extinguishing materials with high resistance to surface tracking
  • Rubber cable gland (cable guide variant only)

Functionality

  • Connection of GET4S, GISS, GME/BS metering units
  • Integrated CT block (200 and 400 kW variants)
  • Wall mounting, with cable guide or inside DS4558, C4M, C3M enclosures

Compliance

  • Enel Technical Specifications DMI031006
  • Fire reaction Class 1 UNI 8457
  • Smoke, toxicity and corrosivity limits according to CEI 20-37 / CEI 20-38

ENEL references

DS 4549, DS 4558, DS 4559.

Versatile Applications

  • Semi-indirect LV installations up to 200–400 kW

  • Electronic metering system connections

  • Retrofit of existing CT assemblies

  • Installations with coaxial cable (with cable guide)

  • Mounting inside standard Enel enclosures

CONTACT US