Outdoor enclosure with LV terminal block 4×95 mm² – N0CE0135

The N0CE0135 outdoor enclosure with LV terminal block 4×95 mm² is designed for pole-mounted or wall-mounted installations in low-voltage distribution networks. Manufactured in high-strength SMC fiberglass and compliant with Enel specifications, it ensures protection, reliability and high performance for copper and aluminium connections.

Outdoor enclosure with LV terminal block 4×95 mm² – N0CE0135

Outdoor enclosure with LV terminal block 4×95 mm²

Parameter Value Unit
Overall dimensions (mm) 400 × 400 × 104
Internal dimensions (mm) 370 × 370 × 78
Material SMC fiberglass – Grey RAL 7001
Reference standards CEI EN 61439-5 (/A1), DS4931 Enel
Flame resistance 80 points – Enel DS4974
Resistance to tracking currents PTI 500 – IEC 60112
Impact resistance 5J – CEI EN 61439-5
Degree of protection IP34D – CEI EN 60529
Terminal block current rating 208 A
Accepted conductors Copper 50 mm², aluminium 95 mm², branch connections up to 35 mm²
Tightening screws M20 (main connection), M14 (branch connection) – stainless steel
Included accessories Support bracket, insulating caps
Cable entries 1 conical + 2 at 90°
Door closure 4 sealable screws
Terminal identification R – S – T – N (neutral terminal with blue screws)

Technical specifications – Outdoor enclosure with LV terminal block 4×95 mm² – N0CE0135

Structure and materials

  • Enclosure made of SMC fiberglass, grey RAL 7001, offering high mechanical strength and resistance to atmospheric agents.
  • Terminal block manufactured in brass P Cu Zn 40 Pb 2 according to UNI EN 12165 CW 617 N.
  • Stainless steel tightening screws: M20 for main connections, M14 for branch connections.
  • Fiberglass cable entries in mixed configuration: one conical gland and two 90° glands.
  • Door fitted with four sealable screws.

Functionality

  • Outdoor installation on pole or wall.
  • Connections with copper conductors up to 50 mm² and aluminium conductors up to 95 mm².
  • Branch connections possible with cables up to 35 mm².
  • Integrated phase separators to ensure adequate insulation between terminals.
  • Phase identification R–S–T–N directly on the terminal block.
  • Total rated current capacity of the terminal block: 208 A.

Compliance

  • CEI EN 61439-5 / A1.
  • Enel specifications DS4931 and DS4524.
  • Flame resistance according to DS4974: >80 points.
  • Impact resistance 5 J (CEI EN 61439-5).
  • Degree of protection IP34D (CEI EN 60529).
  • Compliance with IEC 60112 for resistance to tracking currents (PTI 500).

ENEL references

DS 4524, DS 4931, DS 4974.

Versatile applications

  • Low-voltage secondary substations

  • Branching and connections in LV distribution networks

  • Outdoor pole-mounted or wall-mounted installations

  • Auxiliary distribution panels

  • Industrial and infrastructure electrical systems